Question 21

Which load path connections need to be analyzed when determining live and dead loads on a PV array system installed directly to a metal seam roof?
  • Question 22

    Which of the following voltages should be included on the dc disconnected label to indicate MAXIMUM system voltage?
  • Question 23

    A ground resistance measurement on a newly installed grounding electrode indicates a resistance of 130. The earth connection may be improved by connecting the existing electrode to a:
  • Question 24

    A AWG THWN-2 PV output conductors from two PV arrays are run in the same 3 in, conduit to their respective functionally grounded inverters in the building. The three PV source circuits are each protected by a
    15A fuse in the combiner box at the array. The conduit, which is strapped directly to the roof,is exposed to design temperatures of 140' F (60'C) during its 30 ft.
    Exposed run. What is the MAXIMUM current carrying capability value of the PV output conductors?